OR 6312CTB

or 6312CTB
A Product by Orlab
OverviewSpecificationsResources

pH/Temp Industrial Online Controller 6312PTB


  • Graphic LCD with manual backlight displays conductivity/TDS, temperature, relay status and transmitter current mA output simultaneously.
  • Convenient one point calibration and calibration data is stored in memory and is ready for use on power up.
  • Two sets of Isolated and reversible 4-20 mA current output for conductivity and temperature allows it to be used as a proportional output.
  • 2 programmable on/off relays conductivity.
  • RS-485 output for remote access allows multiple units to be connected and ganged together.
  • Password protection.
  • IP65.
Range (conductivity / TDS) Resolution (conductivity / TDS) Accuracy
K=0.01cm -10.000~9.999uS/cm / 0.000~5.000ppm 0.001uS/cm / 0.001ppm ±0.5%FS±1 digit
10.00~99.99uS/cm / 5.00~50.00ppm 0.01uS/cm / 0.01ppm ±0.5%FS±1 digit
100.0~300.0uS/cm / 50.0~150.0ppm 0.1uS/cm / 0.1ppm ±0.5%FS±1 digit
K=0.1cm -1 10.00~99.99uS/cm / 5.00~50.00ppm 0.01uS/cm / 0.01ppm ±0.5%FS±1 digit
100.0~999.9uS/cm / 50.0~500.0ppm 0.1uS/cm / 0.1ppm ±0.5%FS±1 digit
1.000~3.000mS/cm / 0.500~1.500ppt 0.001mS/cm / 0.001ppt ±0.5%FS±1 digit
K=1.0cm -1 100.0~999.9uS/cm / 50.0~500.0ppm 0.1uS/cm / 0.1ppm ±0.5%FS±1 digit
1.000~9.999mS/cm / 0.500~5.000ppt 0.001mS/cm / 0.001ppt ±0.5%FS±1 digit
10.00~30.00mS/cm / 5.00~15.00ppt 0.01mS/cm / 0.01ppt ±0.5%FS±1 digit
K=10.0cm -1 1.000~9.999mS/cm / 0.000~5.000ppt 0.001mS/cm / 0.001ppt ±0.5%FS±1 digit
10.00~99.99mS/cm / 5.00~50.00ppt 0.01mS/cm / 0.01ppt ±0.5%FS±1 digit
100.0~300.0mS/cm / 50.0~150.0ppt 0.1mS/cm / 0.1ppt ±0.5%FS±1 digit
Temperature -10.0~120.0 0.1 ±0.3
Temperature Compensation Auto -10.0~120.0 (Thermistor, 10K ohm at 25.0 ).
Cell Constant 0.01,0.1, 1.0, 10 cm-1, 2 wire or 4 wire.
Reference Temperature From 10.0 to 29.0 , user selectable.
Temperature Coefficient From 0.00 to 4.99%, user selectable.
Output Two current outputs for conductivity and temperature.
Current Output Range 4 to 20 mA (isolated), programmable span.
Current Output Scale User programmable, linear
Maximum Load / Isolation Voltage 500 ohm / 500V DC.
Control Type / Relay Output 2 ON/OFF controls / 5A at 115V AC or 2.5A at 220V AC, resistive load only.
Display 128 x 64 graphical LCD with backlight.
Security 4-dight password.
Power 115V AC or 230V AC at 50/60 HZ.
Ambient Temperature Range From 0~50 .
Weight / Case 950 grams / IP65, 1/4 DIN case, 148mm depth.
Accessories
392-122 K=0.01cm -1 , range: 0~20uS/cm.
(stainless steel body, POM housing, NPT3/4’’ thread, 5 meters cable, with 10K thermistor).
392-126 K=0.1cm -1, range: 0~200uS/cm.
(stainless steel body, POM housing, NPT3/4’’ thread, 5 meters cable, with 10K thermistor).
392-125 K=1.0cm -1 , range: 0~10mS/cm.
(stainless steel body, POM housing, NPT3/4’’ thread, 5 meters cable, with 10K thermistor).
012-200-00 Waterproof enclosure
Resources